Voltage Drop Calculator

Enter your wire gauge, current, and run length — get the voltage drop, the voltage at the load, and power lost in the cable.

%
Voltage drop
As percent
Load voltage
Power loss

Round-trip voltage drop at 20 °C for the chosen gauge. Need to pick a gauge from scratch instead? Use the wire size calculator. Length unit: .

Where the drop comes from

Every conductor has resistance, and current through it drops voltage — plain Ohm's law applied to the wire. Over a run of length L the drop is:

Vdrop = ρ × (2 × L) × I / A

ρ is the resistivity (copper ≈ 0.0172 Ω·mm²/m, aluminum ≈ 0.0265), L is the one-way length — the current has to get there and back, hence the 2 — I is the current, and A the conductor's cross-sectional area. Thicker wire (bigger A) drops less; longer runs and higher currents drop more.

Worked example

10 A down a 5 m run of 12 AWG copper (≈ 3.31 mm²): Vdrop = 0.0172 × 10 × 10 / 3.31 ≈ 0.52 V — about 4.3% of a 12 V supply, and 5.2 W wasted as heat in the cable. Step up to 10 AWG (≈ 5.26 mm²) and the drop falls to ~0.33 V (2.7%).

How much drop is acceptable?

  • 3% — the usual target for branch circuits feeding a load.
  • 1–2% — sensitive electronics, long sensor runs, solar charge lines where end voltage matters.
  • 5%+ — sometimes fine for lighting or short intermittent loads.

Low-voltage systems feel drop the most: 0.5 V is nothing on 120 V but is over 4% of a 12 V battery, which is why automotive and solar wiring is so thick.

Frequently asked questions

Is this the voltage at my device?
Close — the "load voltage" line is the source voltage minus the drop, the voltage your device actually sees. It ignores the load's own behavior and connector resistance, which add a little more.
Why one-way length, not total?
You enter the one-way run; the formula doubles it because current flows out on one conductor and back on the other, so it crosses twice the length of copper.
Does this account for wire heating?
No — it's the drop at 20 °C. Hot conductors have slightly higher resistance (and thus drop). It's also not an ampacity/code check: a wire can be within its current rating yet still drop too much over a long run. Use the wire size calculator to pick a gauge by drop, and your electrical code for ampacity.
Copper or aluminum?
Aluminum has about 1.5× the resistivity, so for the same drop it needs roughly 1.5× the cross-section — and connectors rated for aluminum.