Wire Size Calculator

Find the minimum wire gauge for your voltage, current, and run length — sized by voltage drop, for copper or aluminum.

%
Minimum size
Actual drop
Power loss

Sized by round-trip voltage drop at 20 °C. This is a design aid for low-voltage DC wiring (automotive, solar, battery) — for mains wiring, follow your electrical code's ampacity tables, not this tool.

How wire sizing by voltage drop works

Wire has resistance, and current through resistance costs voltage. The drop over a run is:

Vdrop = ρ × (2 × L) × I / A

where ρ is the conductor's resistivity (copper ≈ 0.0172 Ω·mm²/m, aluminum ≈ 0.0265), L is the one-way length (current travels out and back, hence the 2), I is the current, and A the cross-sectional area. This calculator inverts that: given your maximum acceptable drop, it finds the smallest standard conductor whose area keeps you under it — plus a table of neighboring sizes so you can see what stepping up or down costs.

Worked example

A 12 V fridge drawing 20 A at the end of a 5 m run, allowing 3% drop (0.36 V): required area = 0.0172 × 10 × 20 / 0.36 ≈ 9.6 mm², so 8 AWG (≈ 8.4 mm²) falls short and 7 AWG (≈ 10.6 mm²) is the smallest that passes — it drops 0.33 V (2.7%) and wastes about 6.5 W in the cable. Odd gauges are rare in stores, so in practice you'd buy 6 AWG; the table above shows both.

Choosing a drop budget

  • 3% — the common target for low-voltage circuits feeding real loads.
  • 1–2% — chargers, sense lines, and anything where the endpoint voltage matters (solar charge controllers especially).
  • 5–10% — sometimes tolerable for lighting or short intermittent loads; know what your device accepts.

Low-voltage systems are unforgiving: 0.5 V is nothing at 120 V but is 4% of a 12 V battery — this is why automotive and solar wiring runs so thick.

Frequently asked questions

Is this the same as ampacity?
No. Ampacity is the current a wire can carry without overheating, set by insulation temperature ratings and installation conditions, and governed by electrical codes (NEC, IEC). A long run often needs a wire far larger than ampacity requires — that's the voltage-drop sizing done here. Always satisfy both: code tables for safety, this calculator for performance.
Does stranded vs solid matter?
For resistance, effectively no — equal total copper area gives equal drop. Stranded is just easier to route and survives vibration better.
What about aluminum wire?
Fine when sized for it (about 1.5× the copper area for the same drop) and terminated with connectors rated for aluminum — oxidation at terminations, not the metal itself, is the classic failure.
Where do the AWG areas come from?
The exact AWG geometric progression: diameter = 0.127 mm × 92^((36−g)/39). Every area in the table is computed from that, not looked up loosely.